Your construction project could burn through a 1,000-gallon fuel tank in three days, or you could go two weeks between deliveries. How do you know where you’ll fall on the spectrum? Here's how to work backward from usage to find the right size.
First, estimate the gallons consumed by every machine that will draw from the tank. Use equipment fuel records or manufacturer burn-rate estimates alongside expected operating hours.
Then calculate your required capacity:
Tank Capacity = Weekly Fuel Consumption × Delivery Interval in Weeks × 1.15
The extra 15% is an old rule of thumb. Basically, it’s your buffer for unexpected consumption or delivery delays.
For example, suppose your equipment uses 800 gallons weekly and your supplier delivers every two weeks.
800 × 2 × 1.15 = 1,840 gallons
Your on-site diesel fuel tank needs at least 1,840 gallons of usable capacity. This calculation is just a planning estimate, of course. Talk to your provider for advice on final tank specification.
A tank's advertised capacity represents its total volume. However, the total rated volume is not all usable. Remember to account for usable vs. total capacity in the tank. The bottom 10% is typically out of reach for the fuel pump, and the top 10% must remain empty for expansion and regulations.
Under these assumptions, only 80% of the rated volume is usable.
Rated Tank Capacity |
Estimated Usable Fuel at 80% |
|
500 gallons |
400 gallons |
|
1,000 gallons |
800 gallons |
|
2,000 gallons |
1,600 gallons |
|
3,000 gallons |
2,400 gallons |
These percentages are illustrative. Actual usable capacity depends on tank construction and pump configuration. Your supplier should confirm the tank's allowable fill level and usable volume.
In the previous example, a 2,000-gallon tank would fall short under the 80% assumption. A larger option would be necessary.
Under the EPA's Spill Prevention, Control, and Countermeasure requirements, facilities with more than 1,320 gallons of aggregate aboveground oil storage capacity are potentially subject to SPCC regulations.
The threshold applies to total applicable storage capacity across the facility rather than the amount of fuel currently inside one tank. Other applicability conditions may also apply.
Review the requirements with your fuel provider when selecting larger construction fuel storage tanks.
Fuel consumption is the foundation for tank sizing, but here are a few of the operational details that could influence your final decision.
Whatley Oil supplies on-site fuel tank rentals and diesel delivery for contractors throughout Georgia and Alabama.
Share your equipment usage and expected delivery schedule with our team. We're ready to help you identify an appropriate tank capacity and plan replenishment around your project.
Contact us today to discuss fuel tank rental and delivery and get started!